| parameter | MD-04 |
| Rated operating parameters | |
| Rated operating cycle | O-0.3s-CO-15s-CO |
| Number of operations per hour | 100 |
| auxiliary voltage | DC48V |
| Auxiliary voltage range | 80%-120% |
| Power consumption | |
| Charging power consumption of switching capacitor | 50W |
| standby power consumption | <4.6W |
| Time characteristics | |
| ***Capacitor charging time after power-on | <5s |
| Capacitor charging time after standard operating cycle | <5s |
| Insulation strength | |
| Power frequency withstand voltage, 60s | 2kV |
| Impact resistance, 40µs/50µs/0.5 J (IEC 60 255-5) | 5kV |
| Insulation resistance, 1000V or 2000VDC | >5MΩ |
| Relay node | |
| Relay node breaking capacity | 250V AC 16A, 250V DC 0.15A |
| Dry node of opening and closing operation | |
| Time to receive opening and closing commands | >12ms |
| Control module dry joint fracture forging | 24V |
| Electromagnetic compatibility | |
| Electrical Fast Pulse Immunity, IEC6100-4-4 Class IV | 4kV |
| Oscillation immunity, IEC61000-4-12 IEC60255-22-1, Level III | 2.5 kV 1MHz, to ground; 1 kV 1MHz, between terminals |
| Surge immunity, IEC61000-4-5, Class IV | 4 kV 1.2/50us, to ground; 2 kV 1.2/50us, between terminals. |
| Impulse magnetic field immunity, IEC61000-4-9, Class V | 1000A/m |